Features
- Built-in wire-saving FRnet control
- High-speed transmission reliability
- Simple synchronization mechanism
- No software overhead on protocol processing
- Supporting broadcasting (1:n data transmission)
- Duplicating output easily
- Fixed I/O scan-time and I/O synchronization
- DIN-Rail mountable
- Analog Input
- Input Channels: 8 differential or 16 single-ended, switch selectable
- Input Type:
+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V
+/-20 mA , 0~20 mA, 4~20 mA (requires optional external 125 Ω resistor for current input) - Resolution: 16-bit (1 channel) / 12-bit (8/16 channels)
- Sampling Rate:
10 samples/ second (1 channel)
50 samples/ second(8/16 channels) total - Accuracy:
+/-0.1% (1 channel)
+/-0.5%(8/16 channels) or better - Bandwidth:
15.7 Hz (1 channel)
78.7 Hz (8/16 channels) - Zero Drift: +/-20 uV/°C
- Span Drift: +/-25 ppm/°C
- Input Impedance:
Voltage: 2 MΩ (Differential), 1 MΩ (Single-ended) - Common Mode Rejection: 86 dB min.
- Normal Mode Rejection: 100 dB
- Individual Channel Configuration: Yes (by software, requires optional CA-0904 cable)
- Over Voltage Protection:
Differential: 240 Vrms, Single-ended: 150 Vrms - Connection: 20-Pin Removable Terminal Block
- Interface
- Isolation Voltage: 3000 Vrms
- 2-wire Cabling: Belden 8941 (2P twisted-pair cable),
When different cables are used, the transmission distance may be changed - Transfer Distance:
Max. 400 m for speed 250 K
Max. 100 m for speed 1 M (Default) - LED Indicators:
Power, Communication Run, Communication Error, Terminal resistor, Digital output - Transfer Speed: 250Kbps and 1Mbps (Default)
- DIP Switch Selectable Cyclic Scan Time:
2.88 ms for speed 250 K
0.72 ms for speed 1 M (Default) - Power
- Input Voltage Range: +10 ~ +30 Vdc (Non-isolation)
- Power Consumption: 2.4 W Max
- Connector: 5-Pin Removable Terminal Block
- EMS Protection
- ESD (IEC 61000-4-2):
4 kV contact for power line, communication line and each channel
8 kV air for random point - EFT (IEC 61000-4-4): 4 kV for power liner
- Surge (IEC 61000-4-5): 3 kV for power liner
- Mechanical
- Mechanical: Plastic
- Flammability: UL 94V-0 materials
- Dimensions (W x H x D): 32.5 x 110 x 102 mm
- Installation: DIN-Rail
- Environment
- Operating Temperature: -25 ~ +75°C
- Storage Temperature: -30 ~ +85°C
- Humidity: 10 ~ 90%, non-condensing
- FR-2017iT – 8/16-channel Isolated Analog Input Module With High Voltage Protection And Isolated Communication Line
Jeśli potrzebujesz dodatkowych informacji zadzwoń do nas (22 831 10 42) lub napisz wiadomość.
Podobne produkty
Gwarancja 24 miesiące - Gwarancja udzielana przez sprzedawcę na okres 24 miesięcy.
Gwarancja standardowa 24 miesiące
Opinie użytkowników